Key Features
- Compact design made it fits everywhere and quick to install
- Its modular architecture assures fast to service and Simple to maintain
- Patented ECOnversion meets Class 1 of IEC® 62040-3: zero-break transfer during power outage and ensure highest energy savings without sacrificing load protection.
- Robust, fault-tolerant design ensures continuous protection in critical circumstances
- Designed to perform in dusty environments with its high-quality air filter and IP20 rating (optional IP52 kit available for select models) Withstands 40ºC operating temperature without derating (50ºC with derating)
- Suited for humid environments thanks to conformal coating
- Seismic certified (with option kit)
- Maximum short circuit rating: 65 kA
- Exceeds industry standards on electromagnetic protection due to EMC Level C2
- Faster battery charging capabilities restore back-up time 2-to-3 times faster compared to industry standards
- Operates at high elevation, with no derating up to 3000m (5000m with derating)
- Models with halogen-free power cables available Unity Power Factor (PF=1) allows for right-size protection to real IT needs
- Well suited for different applications thanks to high flexibility on power factor and high overload capability
- Seamlessly integrates into the electrical environment, with single and dual mains support included
- Optimized uptime with wide input tolerance window (+/-15%)
- Right-sized batteries with flexible DC bus
- One extra power module for N+1 internal redundancy keeps your load
- protected and multiplies system availability by 10 with no extra footprint
- Optimized uptime with wide input tolerance window (+/-15%)
- With Live Swap*, it is simple and fast to add, replace, or remove power modules
- N+0 or N+1 module-level redundancN+0 or N+1 system-level redundancy (parallel up to 4 UPSs)
Technical Specification
Main Input Voltage | 400 V 3 phases |
---|---|
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phases |
Other Output Voltage | 380 V 415 V |
rated power in W | 50 kW |
rated power in VA | 50 kVA |
output connector type | Hard wire 5-wire (3P + N + E) 1 |
battery type | External battery system Li-Ion (Lithium-Ion) VRLA |
provided equipment | Dust filter Installation guide Integrated network management Power modules ship installed Start-up service Top and bottom cable entry |
bypass voltage tolerance | +/- 10 % |
---|---|
max bypass input current | 80 A |
redundant | No |
colour | White |
---|---|
height | 148.5 cm |
width | 52.1 cm |
depth | 84.7 cm |
net weight | 210 kg |
USB compatible | No |
network frequency | 40...70 Hz |
---|---|
number of input connectors | 1 hard wire 4-wire (3P + E) 1 hard wire 5-wire (3P + N + E) |
input voltage limits | 340...460 V 400 V |
maximum input current | 91 A |
max short time withstand current | 65 kA |
input harmonic distortion | Less than 3 % for full load |
load power factor | From 0.7 leading to 0.7 lagging without any derating |
Input Power Factor at Full Load | 0.99 |
Maximum configurable power in W | 50 kW |
---|---|
harmonic distortion | Less than 3 % |
output frequency | 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
crest factor | 2.5 |
Wave type | Sine wave |
output voltage tolerance | +/-1% after 50ms |
output harmonic distortion | < 1% linear load and < 3% non-linear load |
output overload operation | 10 minutes at 125% and 60 seconds at 150% |
bypass type | Built-in static bypass |
Maximum configurable power in VA | 50 kVA |
product certifications | FCC part 15 class A UL 1778 5th edition |
---|---|
standards | CSA C22.2 No 107.3 EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 IEC 60721-4-2 level 2M2 |
ambient air temperature for operation | 0…40 °C |
---|---|
relative humidity | 0…95 % non-condensing |
operating altitude | 0...3281 ft |
ambient air temperature for storage | -25…55 °C |
storage Relative Humidity | Non-condensing 10…80 % |
storage altitude | 0.00…15240.00 m |
acoustic level | 65 dBA |
heat dissipation | 4915.1 Btu/h |
IP degree of protection | IP21 |
battery voltage | 480...576 V DC |
---|---|
discharge battery voltage | 384 V DC |
max current discharge | 136 A |
Battery power in VAH | 0 VAh runtime |
extended runtime | 0 |
free slots | 1 |
---|---|
control panel | Touch screen LCD user interface |
alarm | Audible and visible alarms prioritized by severity |
Package 1 Weight | 235 kg |
---|---|
Package 1 Height | 168 cm |
Package 1 width | 64 cm |
Package 1 Length | 99 cm |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
---|